R1000 - Temperature Controller
Clarian R1000 (PDF datasheet). Product enquiry and further information (Contact us form).
The R1000, R1040 and R1080 1-zone temperature controllers are equipped with a new operating concept that guides you clearly and comfortably through the configuration process with an extended range of functions. In control operation, LEDs signal the most important activities. Setpoint and actual values are easily read off the highly-illuminated four-digit display, even at greater distances. Both appliances have digital and relay outputs, so they can be used for a wide range of different applications.
R1000, R1040 and R1080 differ in terms of their housing format, but identical in all other product features.
Technical Data
Input PT100 (RTD)
- 2- or 3-wire connection possible
- Built-in protection against sensor break and short circuit
- Sensor current: < 0,5 mA
- Calibration accuracy: … < 0,2 % Linear error: … < 0,2 %
- Influence of the ambient temperature: … < 0,01 % / K
Input Thermocouple
- Built-in internal compensation point and protection against sensor break and incorrect polarity.
- Re-calibration not required for a line resistance of up to 50 Ohm.
- Calibration accuracy: … < 0,25 % Linear error: … < 0,2 %
- Influence of the ambient temperature: … < 0,01 % / K
- Influence of the resistance of the sensor cable on the measured voltage: <5uV at 10 Ohm. The resulting temperature error depends on the sensor type.
Output logic
- Voltage signal, 0 / 9,5 V DC, max. 10 mA, short-circuit proof
Outputs relay
- Relay, max. 250 VAC, max. 2 A (resistive load)
- For control loops requiring a high switching frequency of the control output it is recommended to use the logic output controlling a SSR.
7-Segment-Display:
- 4 digits, Process: 10 mm red, Set: 10 mm red
Data protection
CE-mark
- Tested according to: EN61326-2013 Class A / EN61000-3-2:2014 / EN61000-3-3:2013
- Electrical safety: EN 61010-1
Power supply
- Depends on the version of the device:
- - 85 - 264 V AC, 48...62 Hz; approx. 3VA
- - 24 V DC, +/-25 %, approx. 3W
Connections
- Plug in terminals,
- Protection mode IP 20 (DIN 40050), Insulation class I
- Conductor cross section terminals 1-7: 0,2 ? 2,5mm? (AWG: 30 - 12)
- Conductor cross section terminals 9-15: 0,14 ? 1,5mm? (AWG 28 - 16)
Permissible operating conditions
- Operating temperature: 0 … 50°C / 32 … 122°F
- Storage temperature: -30 … 70°C / -22 … 158°F
- Climate class: KWF DIN 40040; equivalent to annual average max. 75 % rel. humidity, no condensation
Casing
- Material: Noryl, self-extinguishing, non-drip, UL 94-V1
- Protection mode: IP 20 (DIN 40050), IP 50 front side
- Case: DIN 43700, installation depth approx. 60 mm
- Format R1000:
- 96 x 96 mm
- Panel cutout: 92 +0,5 mm x 92 +0,5 mm
- Format R1040:
- 48 x 96 mm
- Panel cutout: 45 +0,6 mm x 92 +0,8 mm
- Format R1080:
- 96 x 48 mm
- Panel cutout: 92 +0,8 mm x 45 +0,6 mm
Weight
- Approx. 350 g depending on the version of the device
Subject to technical improvements.