R1120 - Temperature Controller
Clarian R1120 (PDF datasheet). Product enquiry and further information (Contact us form).
The R1120 PID controller features a sophisticated control function. All essential settings are shown on the two 7-segment displays and are easily adjusted using the rotary switch. The 2-point or 3-point controller is also available as a variant with 3-point step control. Further feature. With an optional seal the housing front can achieve a protection class of IP54. Further characteristics: Self-optimising
Technical Data
Input Thermocouple:
- Built-in internal compensation point and protection against sensor break and incorrect polarity.
- Re-calibration not required for a line resistance of up to 50 ohm.
- Calibration accuracy: < 0,25 %
Input RTD, Pt 100 (DIN):
- 2- or 3-wire connection possible.
- Built-in protection against sensor break and short circuit.
- Max. permissible line resistance by 3-wire connection: 80 ohm
- Sensor current: < 0,5 mA
- Calibration accuracy: < 0,2 %
Linear error:
Influence of the ambient temperature:
OUT 1:
- R1120-10?: Relay, (n/o contact) max. 250 V AC, max. 3 A (resistive load)
- R1120-20?: bist. voltage signal, 0/18 V DC, max. 10 mA, short-circuit proof
OUT 2:
- Relay, (n/o contact) max. 250 V AC, max. 3 A (resistive load)
OUT 3:
- Relay, (n/o contact) max. 250 V AC, max. 3 A (resistive load)
7-Segment-Display:
- Process: 10 mm red, Set: 10 mm red
Data protection:
CE-mark:
- EMC: 2004/108/EC, EN 61326-1 for industrial areas
- EN 61010-1
Power supply:
- Standard: 230 V AC, ± 10 %, 48...62 Hz
Connections:
- Plug-in screw terminals, Protection mode IP 20 (DIN 40050), Insulation class C
Permissible operating conditions:
- Operating temperature: 0...50 °C / 32...122 °F
- Storage temperature: -30...70 °C / -22...158 °F
- Climate class: KWF DIN 40040; equivalent to annual average max. 75 % rel. humidity, no condensation
Casing:
- Format: 96 x 96 mm (DIN 43700), installation depth 67 mm
- Panel cutout: 92 +0,5 mm x 92 +0,5 mm
- Material: Noryl, self-extinguishing, non-drip, UL 94-V1
- Protection mode: IP 20 (DIN 40050), IP 50 front side
Further feature:
- With an optional seal the housing front can achieve a protection class of IP54.
Further characteristics:
Weight:
Subject to technical improvements.