R1140 Modular Temperature Controller
Clarian R1140 - 2/3-point controller (PDF datasheet). Product enquiry and further information (Contact us form).
Clarian R1140 - 3-point step controller (PDF datasheet).
Clarian R1140 - 2/3-point controller with interface (PDF datasheet).
The R1140 is a modular temperature controller with numerous configuration and expansion options, e.g., as 2/3-point controller, continuous controller and, equipped with field bus interfaces, like a data professional.
Technical Data
Input Thermocouple:
- Built-in internal compensation point and protection against sensor breakage and incorrect polarity.
- Re-calibration not required for a line resistance of up to 50 Ohms.
- Calibration accuracy:
- Error of compensation point:
Input RTD:
- Built-in protection against sensor breakage and short circuit.
- Max. permissible line resistance by 3-wire connection: 80 Ohms
- Sensor current:
- Calibration accuracy:
Input 0/4-20mA:
Input 0-10VDC:
Linear error:
Influence of the ambient temperature:
Setpoint selection (k1):
- Ext. potential-free contact, switching voltage appr. 24 V dc, max. 1 mA.
- Selection between SP1 (main setpoint) and SP2.
Outputs:
- Version 10:
- Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load)
- Logic / bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof
- Version 60:
- Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load)
- Logic / bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof
- Continuous output: 0/4...20 mA, Load max. 500 Ohm Linearity: < 1,5 %, Delay time: app. 2 secs.
- Version 61:
- Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load)
- Logic / bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof
- Continuous output: 0...10V, input resistance of receiver > 50kOhm Linearity: < 1,5 %, Delay time: app. 2 secs.
Alarm output OUT 2:
- Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load).
- Only for 2-point-controller and continuous-controller configuration.
Alarm output OUT 3:
- Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load).
Process output OUT 4:
- Only version R11x0-60/61. Output range according to the choosen measurement range.
- 0/4…20mA (-60) or 0…10V (-61)
7-Segment-Display:
- Process: 10 mm red, Set: 10 mm red
Data protection:
CE-Mark
- Tested according to 2004/108/EC; EN 61326-1
- Electr. safety: EN 61010-1
Power supply:
- Standard: 230 V AC. ± 10 %, 48...62 Hz. Others possible. See Type Code.
Connections:
- Screw terminals (UR appr.).
- Protection mode IP 20 (DIN 40050), Insulation class C.
Permissible operating conditions:
- Operating temperature: 0...50 °C / 32...122 °F
- Storage temperature: -30...70 °C / -22...158 °F
- Climate class: KWF DIN 40040;
- Equivalent to annual average max. 75 % rel. humidity.
- No condensation.
Casing:
- R1140-Format:
- 48 x 96 mm (DIN 43700). Installation depth 122 mm
- Panel cutout: 45 +0,6 mm x 92 +0,8 mm
- R1180-Format:
- 96 x 48 mm (DIN 43700). Installation depth 122 mm
- Panel cutout: 92 +0,8 mm x 45 +0,6 mm
- Material: Noryl, self-extinguishing, non-drip, UL 94-V1
- Protection mode: IP 20 (DIN 40050), IP 50 front side
- Front side IP 54: Option
Weight:
Subject to technical improvments!