R1140 Modular Temperature Controller
      
      Clarian R1140 - 2/3-point controller (PDF datasheet). Product enquiry and further information (Contact us form).
      Clarian R1140 - 3-point step controller  (PDF datasheet). 
      Clarian R1140 - 2/3-point controller with interface (PDF datasheet). 
The R1140 is a modular temperature controller with numerous configuration and expansion options, e.g., as 2/3-point controller, continuous controller and, equipped with field bus interfaces, like a data professional.      
Technical Data
      
        
          
            Input Thermocouple:
            
              -  Built-in internal compensation point and protection against sensor breakage and incorrect polarity. 
 
              - Re-calibration not required for a line resistance of up to 50 Ohms.
 
              -  Calibration accuracy:
                
              
 
              - Error of compensation point: 
                
              
 
            
             Input RTD: 
            
              - Built-in protection against sensor breakage and short circuit. 
 
              - Max. permissible line resistance by 3-wire connection: 80 Ohms 
 
              - Sensor current: 
                
              
 
              - Calibration accuracy:
                
              
 
            
             Input 0/4-20mA:
            
             Input 0-10VDC:
            
            Linear error: 
            
            Influence of the ambient temperature: 
            
            Setpoint selection (k1):
            
              -  Ext. potential-free contact, switching voltage appr. 24 V dc, max. 1 mA. 
 
              - Selection between SP1 (main setpoint) and SP2. 
 
            
            Outputs: 
            
              - Version 10: 
                
                  - Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load) 
 
                  -  Logic / bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof 
 
                
               
              - Version 60: 
                
                  -  Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load) 
 
                  -  Logic / bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof 
 
                  -  Continuous output: 0/4...20 mA, Load max. 500 Ohm Linearity: < 1,5 %, Delay time: app. 2 secs. 
 
                
               
              - Version 61: 
                
                  - Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load) 
 
                  -  Logic / bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof
 
                  -  Continuous output: 0...10V, input resistance of receiver > 50kOhm Linearity: < 1,5 %, Delay time: app. 2 secs. 
 
                
               
            
            Alarm output OUT 2: 
            
              -  Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load). 
 
              - Only for 2-point-controller and continuous-controller configuration.          
 
            
           
         
        
          
            Alarm output OUT 3: 
            
              -  Relay (UR appr.), max. 250 VAC, max. 3 A (resistive load). 
 
            
            Process output OUT 4: 
            
              - Only version R11x0-60/61. Output range according to the choosen measurement range. 
 
              - 0/4…20mA (-60) or 0…10V (-61)
 
            
            7-Segment-Display: 
            
              - Process: 10 mm red, Set: 10 mm red 
 
            
            Data protection: 
            
            CE-Mark 
            
              - Tested according to 2004/108/EC; EN 61326-1
 
              -  Electr. safety: EN 61010-1 
 
            
            Power supply: 
            
              - Standard: 230 V AC. ± 10 %, 48...62 Hz. Others possible. See Type Code. 
 
            
            Connections: 
            
              - Screw terminals (UR appr.). 
 
              - Protection mode IP 20 (DIN 40050), Insulation class C. 
 
            
            Permissible operating conditions: 
            
              - Operating temperature: 0...50 °C / 32...122 °F 
 
              - Storage temperature: -30...70 °C / -22...158 °F 
 
              - Climate class: KWF DIN 40040; 
 
              - Equivalent to annual average max. 75 % rel. humidity. 
 
              - No condensation. 
 
            
            Casing: 
            
              - R1140-Format:
                
                  - 48 x 96 mm (DIN 43700). Installation depth 122 mm 
 
                  - Panel cutout: 45 +0,6 mm x 92 +0,8 mm 
 
                
               
              - R1180-Format:
                
                  - 96 x 48 mm (DIN 43700). Installation depth 122 mm 
 
                  - Panel cutout: 92 +0,8 mm x 45 +0,6 mm 
 
                
               
              - Material: Noryl, self-extinguishing, non-drip, UL 94-V1
 
              -  Protection mode: IP 20 (DIN 40050), IP 50 front side 
 
              - Front side IP 54: Option 
 
            
            Weight:
            
            Subject to technical improvments!