Technical Data
Input Thermocouple:
- Built-in internal compensation point and protection against sensor breakage and incorrect polarity.
- Re-calibration not required for a line resistance of up to 50 Ohms.
- Calibration accuracy: < 0,25%
Input RTD, Pt 100 (DIN):
- 2- or 3- wire connection possible.
- Built-in protection against sensor breakage and short circuit.
- Max. permissible line resistance by 3-wire connection: 80 Ohms
- Sensor current: < 0,5 mA
- Calibration accuracy: < 0,2 %
Linear error: < 0,2 %
Influence of the ambient temperature: < 0,01 % / K
Setpoint selection:
Ext. potential-free contact, switching voltage appr. 24 V dc, max. 1 mA. Selection between SP1 and SP2 or between SP1 and the analogue setpoint signal SPA.
Control outputs:
- OUT 1:
- Relay (UR appr.), (changeover contact) max. 250 Vac, max. 3 A (resistive load) and bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof
- OUT 2:
- Relay (UR appr.), (changeover contact) max. 250 Vac, max. 3 A (resistive load) and bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof
- OUT 4 or OUT 5:
- Continuous ( version > R1300-2) The output signal (current or voltage) is determinated automatically, dependand on load.
- 0/4...20 mA, load of max. 500 Ohm
- 0/2...10 V dc, load of > 1 k-Ohm
- Linearity: < 1,5 %
- Delay time: app. 2 secs.
Alarm output:
- OUT 2:
- Relay (UR appr.), (changeover contact) max. 250 Vac, max. 3 A (resistive load). Only for 2-point-controller and continuous-controller configuration.
- OUT 3:
- Relay (UR appr.), (changeover contact) max. 250 Vac, max. 3 A (resistive load).
Setpoint input:
(analogue)
- (Only version R1300-3), equivalent to the choosen range
- 0...10 V dc
- 0...20 mA
- 4...20 mA
Process output:
(analogue)
- OUT4 or OUT5:
- (Only version R1300-3), equivalent to the choosen range
- 0...10 V dc
- 0...20 mA
- 4...20mA
- Load max. 500 Ohms