Technical Data
             Input Thermocouple: 
            
              - Built-in internal compensation point and protection against sensor breakage and incorrect polarity. 
 
              - Re-calibration not required for a line resistance of up to 50 Ohms. 
 
              - Calibration accuracy: < 0,25% 
 
            
            Input RTD, Pt 100 (DIN): 
            
              - 2- or 3- wire connection possible.
 
              -  Built-in protection against sensor breakage and short circuit. 
 
              - Max. permissible line resistance by 3-wire connection: 80 Ohms
 
              -  Sensor current: < 0,5 mA
 
              -  Calibration accuracy: < 0,2 % 
 
            
            Linear error: < 0,2 %
             Influence of the ambient temperature: < 0,01 % / K 
            Setpoint selection: 
            Ext. potential-free contact, switching voltage appr. 24 V dc, max. 1 mA. Selection between SP1 and SP2 or between SP1 and the analogue setpoint signal SPA. 
            Control outputs: 
            
              - OUT 1: 
                
                  - Relay (UR appr.), (changeover contact) max. 250 Vac, max. 3 A (resistive load) and bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof 
 
                
               
              - OUT 2:
                  - Relay (UR appr.), (changeover contact) max. 250 Vac, max. 3 A (resistive load) and bist. voltage signal, 0/18 V dc, max. 10 mA, short-circuit proof 
 
                
               
              - OUT 4 or OUT 5:
                  - Continuous ( version > R1300-2) The output signal (current or voltage) is determinated automatically, dependand on load.
 
                  -  0/4...20 mA, load of max. 500 Ohm
 
                  -  0/2...10 V dc, load of > 1 k-Ohm 
 
                  - Linearity: < 1,5 %
 
                  -  Delay time: app. 2 secs.
 
                
               
            
             Alarm output: 
            
              - OUT 2:
                  - Relay (UR appr.), (changeover contact) max. 250 Vac, max. 3 A (resistive load). Only for 2-point-controller and continuous-controller configuration. 
 
                
               
              - OUT 3:
                  - Relay (UR appr.), (changeover contact) max. 250 Vac, max. 3 A (resistive load). 
 
                
               
            
            Setpoint input: 
              (analogue)            
            
              - (Only version R1300-3), equivalent to the choosen range
 
              - 0...10 V dc 
 
              - 0...20 mA
 
              -  4...20 mA 
 
            
            Process output: 
              (analogue)            
            
              - OUT4 or OUT5: 
                
                  - (Only version R1300-3), equivalent to the choosen range            
 
                  - 0...10 V dc 
 
                  - 0...20 mA 
 
                  - 4...20mA 
 
                  - Load max. 500 Ohms